Lesson 4 · Beginner · 8 min read

Which cable size and breaker do I need?

Work out the current, pick a breaker at or just above it, then use a cable that can carry at least what the breaker lets through. In much of Europe that means 1.5 mm² on 10 A for lights and 2.5 mm² on 16 A for sockets. Long runs and hot spots need a thicker cable.

Current15.2 Aat 230 V
BreakerB16the next size up
Cable2.5 mm²voltage drop 2.4%

Typical values for copper cable run in a wall. The real size also depends on how the cable is laid and on your local rules.

Three numbers that must line up

Every circuit has three numbers, and they must go up in this order:

1The load

How many amps the things on the circuit draw. Watts ÷ volts.

2The breaker

Equal to or above the load, so it does not trip in normal use.

3The cable

Able to carry at least what the breaker lets through, all day, without overheating.

The breaker is there to protect the cable. If the cable can safely carry 20 A and the breaker is 16 A, the cable can never be overloaded. Swap in a 32 A breaker and the same cable can cook inside the wall before anything trips.

That is also why a socket circuit gets a 16 A breaker even if you only plan to plug in a lamp: you can never know what someone will plug in later.

Typical sizes

CircuitBreakerCable
LightsB101.5 mm²
SocketsB162.5 mm², or 1.5 mm² where local rules allow it, as in Germany
Oven, dishwasher, washing machineB16, one circuit each2.5 mm²
Hob3 × B16 three-phase, or B325 × 2.5 mm², or 6 mm²
Car charger, 7 kWB32 or C326 mm²

Typical values for copper. Local rules always decide.

Ad300 × 250

When to go thicker

  • Long runs. Every metre of wire has a little resistance. Over a long distance the voltage drops, and the far end gets less.
  • Packed or covered cables. A cable buried in thermal insulation or bundled with others cannot lose its heat, so it carries less.
  • Hot places. Attics, boiler rooms and outdoor runs in the sun lower what a cable can safely carry.
  • Big loads that run for hours. Heaters, car chargers and water heaters run at full power for a long time. In North America the rule is to size for 125% of a load that runs three hours or more.

Voltage drop, worked out

drop = 2 × length × amps × 0.0225 ÷ size

Length in metres, size in mm². The 2 is there because the current goes out and comes back. 0.0225 is how much a warm copper wire resists, per metre and per mm².

Take a 3,500 W oven, 40 m from the fuse box, on 230 V. That is 15.2 A.

On 2.5 mm²

2 × 40 × 15.2 × 0.0225 ÷ 2.5 = 11 V. That is 4.8% of 230 V, right at the limit.

On 4 mm²

2 × 40 × 15.2 × 0.0225 ÷ 4 = 6.8 V. Only 3.0%. The better choice.

Many rules aim for a drop of no more than about 3% on lighting and 5% on everything else.

mm² or AWG?

Europe, the UK and Australia give the copper area in square millimetres: bigger number, thicker wire. North America uses AWG gauge numbers, where it is the other way round: a smaller number means a thicker wire.

AWGCopper areaClosest metric size
14 AWG2.1 mm²2.5 mm²
12 AWG3.3 mm²4 mm²
10 AWG5.3 mm²6 mm²
8 AWG8.4 mm²10 mm²

Common mistakes

  • Fitting a bigger breaker because the old one keeps tripping. The breaker was doing its job, and now nothing protects the cable.
  • Mixing up circuits. Extending a socket from a lighting circuit puts a socket's load on cable and a breaker that were sized for lamps.
  • Forgetting the length. A cable that is fine for 10 m can be too thin for 50 m.
  • Running a heater from a coiled extension reel. The coil traps the heat and can melt. Unroll it fully.
Try it in the sandboxWire a long socket circuit, load it up and see how the breaker and the cable size work together.
Open the sandbox
Next · Lesson 5Reading a cable