Which cable size and breaker do I need?
Work out the current, pick a breaker at or just above it, then use a cable that can carry at least what the breaker lets through. In much of Europe that means 1.5 mm² on 10 A for lights and 2.5 mm² on 16 A for sockets. Long runs and hot spots need a thicker cable.
Typical values for copper cable run in a wall. The real size also depends on how the cable is laid and on your local rules.
Three numbers that must line up
Every circuit has three numbers, and they must go up in this order:
How many amps the things on the circuit draw. Watts ÷ volts.
Equal to or above the load, so it does not trip in normal use.
Able to carry at least what the breaker lets through, all day, without overheating.
The breaker is there to protect the cable. If the cable can safely carry 20 A and the breaker is 16 A, the cable can never be overloaded. Swap in a 32 A breaker and the same cable can cook inside the wall before anything trips.
That is also why a socket circuit gets a 16 A breaker even if you only plan to plug in a lamp: you can never know what someone will plug in later.
Typical sizes
| Circuit | Breaker | Cable |
|---|---|---|
| Lights | B10 | 1.5 mm² |
| Sockets | B16 | 2.5 mm², or 1.5 mm² where local rules allow it, as in Germany |
| Oven, dishwasher, washing machine | B16, one circuit each | 2.5 mm² |
| Hob | 3 × B16 three-phase, or B32 | 5 × 2.5 mm², or 6 mm² |
| Car charger, 7 kW | B32 or C32 | 6 mm² |
| Circuit | Breaker | Cable |
|---|---|---|
| Lights | 6 A | 1.0 or 1.5 mm² |
| Sockets, ring | 32 A | 2.5 mm² in a loop |
| Sockets, radial | 20 A | 2.5 mm² |
| Cooker | 32 to 40 A | 6 mm² |
| Electric shower | 40 to 50 A | 10 mm² |
| Circuit | Breaker | Wire |
|---|---|---|
| Lights, general outlets | 15 A | 14 AWG |
| Kitchen and bathroom outlets | 20 A | 12 AWG |
| Clothes dryer, 240 V | 30 A | 10 AWG |
| Range, 240 V | 40 to 50 A | 8 or 6 AWG |
Typical values for copper. Local rules always decide.
When to go thicker
- Long runs. Every metre of wire has a little resistance. Over a long distance the voltage drops, and the far end gets less.
- Packed or covered cables. A cable buried in thermal insulation or bundled with others cannot lose its heat, so it carries less.
- Hot places. Attics, boiler rooms and outdoor runs in the sun lower what a cable can safely carry.
- Big loads that run for hours. Heaters, car chargers and water heaters run at full power for a long time. In North America the rule is to size for 125% of a load that runs three hours or more.
Voltage drop, worked out
drop = 2 × length × amps × 0.0225 ÷ sizeLength in metres, size in mm². The 2 is there because the current goes out and comes back. 0.0225 is how much a warm copper wire resists, per metre and per mm².
Take a 3,500 W oven, 40 m from the fuse box, on 230 V. That is 15.2 A.
2 × 40 × 15.2 × 0.0225 ÷ 2.5 = 11 V. That is 4.8% of 230 V, right at the limit.
2 × 40 × 15.2 × 0.0225 ÷ 4 = 6.8 V. Only 3.0%. The better choice.
Many rules aim for a drop of no more than about 3% on lighting and 5% on everything else.
mm² or AWG?
Europe, the UK and Australia give the copper area in square millimetres: bigger number, thicker wire. North America uses AWG gauge numbers, where it is the other way round: a smaller number means a thicker wire.
| AWG | Copper area | Closest metric size |
|---|---|---|
| 14 AWG | 2.1 mm² | 2.5 mm² |
| 12 AWG | 3.3 mm² | 4 mm² |
| 10 AWG | 5.3 mm² | 6 mm² |
| 8 AWG | 8.4 mm² | 10 mm² |
Common mistakes
- Fitting a bigger breaker because the old one keeps tripping. The breaker was doing its job, and now nothing protects the cable.
- Mixing up circuits. Extending a socket from a lighting circuit puts a socket's load on cable and a breaker that were sized for lamps.
- Forgetting the length. A cable that is fine for 10 m can be too thin for 50 m.
- Running a heater from a coiled extension reel. The coil traps the heat and can melt. Unroll it fully.